In an external mode simulation, you can tune parameters in real time and monitor target application signals. Using the Run on Custom Hardware app, you can set up and run on your development computer or custom hardware external mode simulations that use an XCP communication channel.
For an external mode simulation, you:
Build the target application on your development computer.
Deploy the target application to the target hardware.
Connect Simulink® to the target application that runs on the target hardware.
Start execution of generated code on the target hardware.
Configure and run an external mode simulation that uses the XCP communication protocol. During the simulation:
Monitor a signal by using a Scope block, a Dashboard block, and the Simulation Data Inspector.
Tune a parameter by using a Dashboard block.
Create a folder for this example.
mkdir ext_mode_xcp_example cd ext_mode_xcp_example
Open Simulink and create a simple model, xcpExample
, which contains
these blocks:
Sine Wave
Gain
Scope
Half Gauge
Knob
Double-click the Sine Wave block. Set Sample time to 0.1, and then click OK.
Double-click the Gain block. Set Gain to 2, and then click OK.
Connect the Sine Wave block to the Gain block and
name the connection, for example, Test Signal
.
Connect the Gain block to the Scope block and name
the connection, for example, Output Signal
.
Configure Test Signal
for logging:
Select Test Signal
.
On the Signal tab, in the Monitor section, select Log Signals.
If you do not enable signal logging, you cannot stream Test
Signal
to the Simulation Data Inspector.
Configure the Half Gauge block to monitor the value of
Test Signal
:
Double-click the Half Gauge block.
In the Simulink Editor, select Test Signal
.
In the Block Parameters dialog box:
Connect the block to Test Signal
.
In the Maximum field, enter a value, for example,
1
.
Click OK.
Configure the Knob block to tune the Amplitude parameter of the Sine Wave block:
Double-click the Knob block.
In the Simulink Editor, select the Sine Wave block.
In the Block Parameters dialog box:
Connect the block to the Amplitude parameter of the Sine Wave block.
In the Minimum and Maximum fields, enter values, for example, 0.1 and 1 respectively.
Click OK.
Save the model as xcpExample
.
From the Apps tab on the Simulink toolstrip, in the Setup to Run on Hardware section, click Run on Custom Hardware. On the Run on Custom Hardware pop-up dialog box, click Finish.
In the Hardware section, specify the system target file. For
this example, use the default, grt.tlc
. If you have
Embedded Coder®, you can specify ert.tlc
.
In the Prepare gallery, under Model Configuration, click Hardware Settings. The Configuration Parameters dialog box opens, displaying Hardware Implementation settings that are determined by the system target file.
On the Solver pane:
In the Type field, specify
Fixed-step
.
Under Solver details, in the Fixed-step size field, specify a value, for example, 0.1.
On the Code Generation > Optimization pane, set Default parameter behavior to
Tunable
.
On the Code Generation > Interface pane, select the External mode check box.
Set Transport layer to XCP on
TCP/IP
, which specifies ext_xcp
for
MEX-file name.
You cannot disable the Static memory allocation check box. The Static memory buffer size value specifies the size of XCP slave memory that is allocated for signal logging. For this example, use the default value.
If System target file is ert.tlc
,
on the Code Generation > Templates pane:
Select the Generate an example main program check box.
Set Target operating system to
BareBoardExample
.
Using the documented APIs of the external mode abstraction layer that are
available in
,
the code generator creates an example that shows how you can provide XCP
external mode target connectivity for a bare board that does not run an
operating system.matlabroot
\toolbox\coder\xcp\src\target\ext_mode\include\ext_mode.h
Click OK. Then save the model.
In the Run on Hardware section:
To specify a nondefault value for the simulation stop time, in the
Stop Time field, specify your value, for example,
inf
.
Click . The software:
Builds the target application:
In Windows®, the build process creates:
xcpExample.exe
–– The executable
file.
xcpExample.pdb
–– A debugging symbols file
for signals and parameters.
In Linux®, the build process places DWARF format debugging
information in the created ELF executable file,
xcpExample
.
Runs the target application as separate process on your development computer.
Connects Simulink to the target application.
Runs the generated model code.
To perform the steps separately, click Monitor & Tune. Under Step By Step Commands, click:
Build for Monitoring
Deploy
Connect
Start
You can monitor Test Signal
through the:
Scope block –– Double-click the block.
Simulation Data Inspector –– Click the Simulation Data Inspector button. When the Simulation Data Inspector opens, select the Test Signal check box, which displays streamed data.
Half-Gauge block.
To change the amplitude of the sine wave, rotate the pointer on the Knob block to the required value.
This table describes more ways of tuning tunable block parameters during a simulation.
Approach | Details |
---|---|
Model Data Editor | To tune parameters through the Model Data Editor:
For more information, see Configure Data Properties by Using the Model Data Editor. |
Block Parameter dialog box | To tune parameters through the Block Parameter dialog box:
|
MATLAB® workspace | If block parameters are MATLAB workspace variables:
For more information, see Create and Edit Variables. |
For more information about parameter tuning with generated code, see External Mode Simulation with TCP/IP or Serial Communication and Create Tunable Calibration Parameter in the Generated Code (Embedded Coder).
If your model contains a Stateflow® chart, you can view state activity. For more information, see Animate Stateflow Charts (Stateflow).
To stop the execution of generated model code before StopTime
is
reached and disconnect the target application, on the Simulink Editor toolbar, click the Stop button .
If you want to disconnect the target application from Simulink without stopping code execution, click . Then, under Step By Step Commands,
click Disconnect.
For XCP external mode simulations, you can configure a trigger that starts the uploading of target application data for signal monitoring in Simulink.
In the Simulink Editor, configure these signals for logging by right-clicking each signal and then selecting Log Selected Signals:
test_signal
test_carrier
test_output
cmp_output
From the Apps tab on the Simulink toolstrip, in the Setup to Run on Hardware section, click Run on Custom Hardware. On the Run on Custom Hardware pop-up dialog box, click Finish.
In the Prepare gallery, under Model Configuration, click Hardware Settings.
On the Solver pane, in the Type field,
specify Fixed-step
.
On the Code Generation > Interface pane, select the External mode check box.
Set Transport layer to XCP on
TCP/IP
, which specifies ext_xcp
for MEX-file
name.
Click OK. Then save the model.
To open the External Signal & Triggering dialog box, from the Prepare gallery, under Signal Monitoring & Tracing, click Control Panel.
In the Configuration section, click Signal & Triggering, which opens the External Signal & Triggering dialog box.
Through this dialog box, you can select signals for monitoring and configure the trigger for uploading data from the target application. For this example, use the default settings. For example:
The Select all check box is selected — The dialog box
displays an X
in each row of the Selected
column. You can monitor all logged signals
during the simulation.
Source is set to manual –– The External Mode Control Panel provides manual control of data uploading, for example, the Arm Trigger button.
The Arm when connecting to target check box is selected — When you connect Simulink to the target application, the trigger is armed.
Click OK.
From the Hardware tab in the Simulink Editor, in the Run on Hardware section:
In the Stop Time field, specify your value, for example,
inf
.
Save the model.
Click . The software:
Builds the target application:
Runs the target application as separate process on your development computer.
Connects Simulink to the target application.
Runs the generated model code.
To view the scope displays, double-click ScopeA
and
ScopeB
.
To monitor signals in the Simulation Data Inspector, in the Review Results section, click the Data Inspector button.
From the External Mode Control Panel, you can suspend or resume signal logging and monitoring. In the Connection and triggering section, click Cancel Trigger or Arm Trigger respectively.
To stop the execution of the target application and disconnect Simulink from the target environment, click Stop Real-Time Code.
For information about signal monitoring and trigger options, see XCP External Mode Control Panel and XCP External Signal & Triggering Dialog Box.
You can use commands to run XCP external mode simulations. To retrieve and set the
values of model parameters, use the get_param
and set_param
commands.
To run these commands, you must have a Simulink model open and a target application running.
Set the model simulation mode to external mode.
set_param(gcs,'SimulationMode','external');
Connect Simulink to the target application.
set_param(gcs,'SimulationCommand','connect')
Run generated model code.
set_param(gcs,'SimulationCommand','start');
To tune a parameter, change its workspace variable value through a line command.
For example, if a block parameter value is specified as a
Simulink.Parameter
object, assign the new value to the
Value
property.
myParamObj.Value = 5.23;
To download the new value to the target application, update the model.
set_param(gcs,'SimulationCommand','update');
Stop the target application and disconnect Simulink from the target environment.
set_param(gcs,'SimulationCommand','stop');
To disconnect Simulink from the target application without stopping execution of generated code, use this command:
set_param(gcs,'SimulationCommand','disconnect');
The set_param
commands that use the 'SimulationCommand'
argument are asynchronous. If you run the commands successively from a script, each command
starts without waiting for the previous command to complete. To check that each command is
complete, in the script, use the get_param
command with the
'SimulationStatus'
argument. For example, for steps 1 to 3, specify these
commands in the
script:
set_param(gcs,'SimulationMode','external'); set_param(gcs,'SimulationCommand','connect'); isExternalSimulationActive = false; while ~isExternalSimulationActive simStatus = get_param(gcs, 'SimulationStatus'); isExternalSimulationActive = strcmp(simStatus, 'external'); end set_param(gcs,'SimulationCommand','start');
For more information, see Run Simulations Programmatically.
The Diagnostic Viewer displays error messages produced by the get_param
and set_param
commands.
To support the one-click workflow or Deploy step for custom hardware, register your custom launcher for the target application.
Create an rtw.connectivity.Config
(Embedded Coder) subclass, which requires
myCustomLauncher
, a launcher that you provide.
myCustomLauncher
is a subclass of rtw.connectivity.Launcher
(Embedded Coder). In myCustomLauncher
, to
support one-click functionality, provide an implementation of the
getApplicationStatus
method. For the communicator and builder
subclasses, you can use dummy
classes.
classdef myTargetConnectivityConfig < rtw.connectivity.Config methods % Constructor function this = myTargetConnectivityConfig(componentArgs) % Launcher with port 0 argument to start TCP/IP server on free port modelName = componentArgs.getModelName(); bDirInfo = RTW.getBuildDir(modelName); exeName = fullfile(bDirInfo.CodeGenFolder, modelName); if ispc exeName = [exeName, '.exe']; end launcher = myCustomLauncher(componentArgs); launcher.setExe(exeName); % Create dummy communicator and builder communicator = rtw.connectivity.RtIOStreamHostCommunicator.empty(); builder = rtw.connectivity.MakefileBuilder.empty(); % Call super class constructor to register components this@rtw.connectivity.Config(componentArgs, builder, launcher, communicator); end end end
To register the implementation in Simulink, create an sl_customization.m
file.
function sl_customization(cm) cm.registerTargetInfo(@loc_createConfig); end % local function function config = loc_createConfig config = rtw.connectivity.ConfigRegistry; config.ConfigClass = 'myTargetConnectivityConfig'; % Specify compatible model configuration. For example, % through SystemTargetFile and TargetHWDeviceType properties. config.SystemTargetFile = {'ert.tlc'}; config.TargetHWDeviceType = { 'ARM Compatible->ARM Cortex' }; end
Add the folder containing sl_customization.m
to the search path
and refresh your
customizations.
addpath(sl_customization_path); sl_refresh_customizations;
You can run your target application with optional arguments. You can pass the optional arguments to your target application through your custom launcher implementation.
Argument | Description |
---|---|
-w | Specify that the target application enters and stays in a wait state until it receives a message from Simulink. If you do not specify |
-tf | Override the model parameter Specify
|
For host-based external mode simulations, you can specify additional rtiostream (Embedded Coder)
arguments.
Argument | Description |
---|---|
| Specify verbosity level:
|
| For For On Windows, On Linux, |
| For |
This table describes limitations that apply to external mode simulations that use XCP communication.
Feature | Details |
---|---|
Parameter updates that change model structure | You cannot change:
If you make parameter updates that change the model structure, you must rebuild the target application. You can change numerator and denominator polynomial parameters for the Transfer Fcn, Discrete Transfer Fcn, and Discrete Filter blocks if the number of states does not change. You cannot change zero entries in the State-Space, Zero-Pole, and Discrete Zero-Pole blocks in the user-specified or computed parameters, that is, the A, B, C, and D matrices obtained by a zero-pole to state-space transformation. In the State-Space block, if you specify the matrices in the controllable canonical realization, then changes to the A, B, C, and D matrices that preserve this realization and the dimensions of the matrices are allowed. If the Simulink block diagram does not match the target application, Simulink produces an error stating that the checksums do not match. The checksums take into account the top models, but not referenced models. To rebuild the target application, use the updated block diagram. |
Signal value display | The graphical display of signal values during a simulation is not supported. For example, you cannot use the Data Display in Simulation menu items Show Value Labels When Hovering, Toggle Value Labels When Clicked, and Show Value Label of Selected Port. For more information, see Display Signal Values in Model Diagrams. |
Data archiving | Data Archiving features available on the External Mode Control Panel are not supported. You can use the Simulation Data Inspector to collect and export data. |
Overriding signal logging settings | If you use the Signal Logging Selector to override signal logging settings, the controls to override the Decimation and Limit data points settings are not supported. |
Compiler debug symbol format | Your toolchain must generate debug information in one of these formats:
|
Inlined parameters | If you set |
Global variables | Signals, parameters, and states must be specified as global variables. The target memory locations where the variables are stored must lie in the range 0 – 4294967295. |
Parameter structures | You cannot tune parameters that are structures. |
Pure integer code | Pure integer code is supported. For code generation, if
If
you do not specify If you specify
|
Variable-size signals | Uploading of variable-size signals is not supported. |
Compiler support |
|
Endianess | Target hardware that uses big endian architecture is not supported. |
Address granularity | Target hardware that uses word addresses is not supported. |
Portable word sizes | When the production target hardware is word-addressable, the generation of a host-based target application by using portable word sizes is not supported. The production target hardware must support 8-bit, 16-bit, and 32-bit native data types. |
Scope and Floating Scope blocks, and Scope Viewer | Some signal data types are not supported. The simulation produces a warning. |
Scopes in referenced models | In a model hierarchy, if the top model runs in external mode and a referenced model runs in normal or accelerator mode, scopes in the referenced model are not displayed. To monitor signals within a referenced model, enable signal logging and use the Simulation Data Inspector. |
Nonzero simulation start time | Nonzero simulation start times are not supported. Use the default value
for Solver > Start time, |
Intermediate step values |
Some Simulink blocks can generate multiple values in a simulation time step. For example:
For each time step in an external mode simulation, Simulink uploads from the target application only the final values of such blocks. Simulink does not upload the intermediate values generated during the step. |
File-scoped data | File-scoped data is not supported. For example, data items to which you
apply the built-in custom storage class For more information about the
|
Row-major code generation | Code generated with the row-major format is not supported. |
Concurrent execution | Concurrent execution is not supported. If System target
file is ert.tlc and Target
operating system is NativeThreadsExample ,
you cannot build the target application. |
VxWorks® example | If System target file is
|
Saving simulation output as a single object | Saving the XCP external mode simulation output as a single object is not supported. The simulation produces a warning. |