Specify the timer parameters in the format of tags
. In Ladder
Diagrams, tags (variables) are used for representing all inputs, outputs, and internal
memory with attributes such as Data Type
, Initial
Value
, and size
. To change the attributes of the
Operand Tag
, open the Program Variables table
within the Ladder Diagram Program block. The Data Type
of the timer tag is of the Bus:TIMER
type with its initial value
specified as a structure containing the following fields:
Field | Description | Default Value |
---|
PRE | The preset value specifies the value (1 millisecond units) which
the accumulated value must reach before the instruction indicates it is
done | 0 |
ACC | The accumulated value specifies the number of milliseconds that
have elapsed since the TOF instruction was
enabled. | 0 |
EN | The enable bit contains rung-condition-in when the instruction was
last executed. | 0 |
TT | The timing bit when set indicates the timing operation is in
process. | 0 |
DN | The done bit when set indicates the timing operation is complete
(or paused). | 0 |
Programmatic Use
Block Parameter:
PLCOperandTag |
Type: character vector |
Value: character vector |
Default: 'T' |