Induction Machine (Single-Phase)
Single-phase induction machine with SI or pu fundamental parameterization
Description
The Induction Machine (Single-Phase) block represents a
single-phase induction machine with a squirrel cage rotor with fundamental parameters
expressed in per-unit or in the International System of Units (SI).
Each of four model variants for the Induction Machine
(Single-Phase) block corresponds to a Block
choice option. To access the block choices, in the model window,
right-click the block, and then use either of these methods:
From the context menu, select > .
In the Simulink® Editor, on the Modeling tab, in the
Design section, in the Data Management
category, select Property Inspector. In the Property
Inspector window, select a .
The model variant options are:
The single phase induction machine consists of a squirrel cage rotor and two stator
windings, the main and the auxiliary windings. The auxiliary winding is typically only
active during startup. However, to improve performance, the auxiliary winding can be
active during running for low-power applications. The figure shows the equivalent
d- and q-axis circuits for the main and
auxiliary windings.
The table defines the variables.
Variable | Definition |
---|
vqsvds | Stator voltages in the d-q
representation |
iqsids | Stator currents in the d-q
representation |
ΨqrΨdr | Rotor fluxes in the d-q representation |
⍵ | Rotor electrical speed |
a | Auxiliary/main windings turn ratio |
Ras | Main winding stator resistance |
Las | Main winding stator leakage inductance |
R'ar | Main winding rotor resistance |
L'lar | Main winding rotor leakage inductance |
Lmas | Main winding mutual inductance |
Rbs | Auxiliary winding stator resistance |
Rlbs | Auxiliary winding stator leakage inductance |
R'br | Auxiliary winding rotor resistance |
L'lbr | Auxiliary winding rotor leakage inductance |
Lmbs | Auxiliary winding mutual inductance |
Equations
The SI model converts the SI values that you enter in the dialog box to per-unit
values for simulation. For information on the relationship between SI and per-unit
machine parameters, see Per-Unit Conversion for Machine Parameters. For information on per-unit parameterization, see Per-Unit System of Units.
These transformations reduce the rotor resistance, rotor leakage inductance, and
stator mutual inductance to a single set of values by defining the equivalent
circuits with respect to the main winding:
The voltage equations for the stator and rotor are:
The expression for the electromagnetic torque, T, is obtained by
applying the principle of virtual displacement [1].
The mechanical equation is
where ωm is the rotor
angular velocity.
In split-phase machines, the auxiliary winding is displaced at 90 electrical degrees from
the main winding and operates only until the speed reaches the disconnection speed,
which is typically 70 to 80 percent of rated speed. In this configuration, the
auxiliary winding has high resistance and small reactance compared to the main
winding. The resulting phase difference makes the machine behave like a two-phase
machine.
The capacitor-start machine is a type of split-phase machine that uses a capacitor
in series with the auxiliary winding to start the machine. In this configuration,
auxiliary and main windings have the same number of turns. The value of the
capacitor ensures that the current in the auxiliary coil leads the current in the
main winding by approximately 80 electrical degrees.
The capacitor-start voltage is:
When a capacitor is connected in series with the auxiliary winding, the voltage
equation for the d-axis is
The extension is obtained immediately for capacitor-start-capacitor-run machines. In this
configuration, two capacitors are connected in parallel.
The d-axis voltage after disconnecting the capacitor-start is
Display Option
To display the machine per-unit base values in the MATLAB® Command Window, right-click the block and, from the
menu, select .
Ports
Output
expand all
pu
— Machine per-unit measurements
physical signal | vector
Physical signal vector port associated with the machine per-unit
measurements. The vector elements are:
pu_torque
pu_velocity
pu_vds
pu_vqs
pu_v0s = 0
pu_ids
pu_iqs
pu_i0s = 0
Conserving
expand all
a1
— Main winding positive terminal
electrical | scalar
Electrical conserving port associated with the main winding positive
terminal.
a2
— Main winding negative terminal
electrical | scalar
Electrical conserving port associated with the main winding negative
terminal.
b1
— Auxiliary winding positive terminal
electrical | scalar
Electrical conserving port associated with the auxiliary winding
positive terminal.
Dependencies
This port is visible only if you set the Block choice to
Main and auxiliary windings
.
b2
— Auxiliary winding negative terminal
electrical | scalar
Electrical conserving port associated with the auxiliary winding
negative terminal.
Dependencies
This port is visible only if you set the Block choice to
Main and auxiliary windings
.
R
— Machine rotor
mechanical rotational
Mechanical rotational conserving port associated with the machine
rotor.
C
— Machine case
mechanical rotational
Mechanical rotational conserving port associated with the machine
case.
Parameters
expand all
Main
Rated apparent power
— Rated apparent power
180
V*A
(default) | positive scalar
Rated apparent power of the induction machine.
Rated voltage
— Rated voltage
220
V
(default) | positive scalar
Rated electrical frequency
— Rated electrical frequency
60
Hz
(default) | positive scalar
Nominal electrical frequency corresponding to the rated apparent
power.
Number of pole pairs
— Number of pole pairs
2
(default) | positive integer
Number of machine pole pairs. The value is used as a
back-electromotive force constant.
Parameterization unit
— SI or per-unit parameterization option
SI
(default) | Per unit
Unit system for block parameterization.
Dependencies
Selecting:
Electrical
For the Parameterization unit parameter in the
Main settings, select SI
to
expose the SI Electrical parameters, or Per
unit
to expose the per-unit Electrical
parameters.
Main winding stator resistance, Ras
— Main winding stator resistance
1.8180
Ohm
(default) | positive scalar
SI stator resistance for the main winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Main winding stator leakage inductance, Llas
— Main winding stator leakage inductance
0.0067
H
(default) | positive scalar
SI leakage inductance for the main winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Main winding rotor resistance, Rar'
— Main winding rotor resistance
3.7080
Ohm
(default) | positive scalar
SI rotor resistance for the main winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Main winding rotor leakage inductance, Llar'
— Main winding rotor leakage inductance
0.0050
H
(default) | positive scalar
SI rotor leakage inductance for the main winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Main winding mutual inductance, Lms
— Main winding mutual inductance
0.1595
H
(default) | positive scalar
SI mutual inductance for the main winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Auxiliary winding stator resistance, Rbs
— Auxiliary winding stator resistance
6.4260
Ohm
(default) | positive scalar
SI stator resistance for the auxiliary winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Auxiliary winding stator leakage inductance, Llbs
— Auxiliary winding stator leakage inductance
0.0077
H
(default) | positive scalar
SI stator leakage inductance for the auxiliary winding.
Dependencies
Selecting SI
for the
Parameterization unit parameter in the
Main settings exposes SI
Electrical parameters.
Auxiliary/main windings turn ratio
— Turn ratio
1.1
(default) | positive scalar
Winding ratio between the main and auxiliary winding.
Main winding stator resistance, Ras (pu)
— Main winding stator resistance
0.0135
(default) | positive scalar
Per-unit stator resistance for the main winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Main winding stator leakage inductance, Llas (pu)
— Main winding stator leakage inductance
0.0188
(default) | positive scalar
Per-unit leakage inductance for the main winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Main winding rotor resistance, Rar' (pu)
— Main winding rotor resistance
0.0276
(default) | positive scalar
Per-unit rotor resistance for the main winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Main winding rotor leakage inductance, Llar' (pu)
— Main winding rotor leakage inductance
0.0140
(default) | positive scalar
Per-unit rotor leakage inductance for the main winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Main winding mutual inductance, Lms (pu)
— Main winding mutual inductance
0.4472
(default) | positive scalar
Per-unit mutual inductance for the main winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Auxiliary winding stator resistance, Rbs (pu)
— Auxiliary winding stator resistance
0.0478
(default) | positive scalar
Per-unit stator resistance for the auxiliary winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Auxiliary winding stator leakage inductance, Llbs (pu)
— Auxiliary winding stator leakage inductance
0.0216
(default) | positive scalar
Per-unit stator leakage inductance for the auxiliary winding.
Dependencies
Selecting Per unit
for the
Parameterization unit parameter in the
Main settings exposes per-unit
Electrical parameters.
Auxiliary/main windings turn ratio
— Turn ratio
1.1
(default) | positive scalar
Winding ratio between the main and auxiliary winding.
Capacitor-start resistance, Rs
— Capacitor-start resistance
3
Ohm
(default) | positive scalar
SI capacitor-start resistance.
Dependencies
This parameter is exposed when Block choice
is set to Capacitor-start-capacitor-run
or Capacitor start
and the
Parameterization unit parameter in the
Main settings is set to
SI
.
Capacitor-start capacitance, Cs
— Capacitor-start capacitance
0.00018
F
(default) | positive scalar
SI capacitor-start capacitance.
Dependencies
This parameter is exposed when Block choice
is set to Capacitor-start-capacitor-run
or Capacitor start
and the
Parameterization unit parameter in the
Main settings is set to
SI
.
Capacitor-run resistance, Rr
— Capacitor-run resistance
9
Ohm
(default) | positive scalar
SI capacitor-run resistance.
Dependencies
This parameter is exposed when Block choice
is set to Capacitor-start-capacitor-run
and the Parameterization unit parameter in the
Main settings is set to
SI
.
Capacitor-run capacitance, Cr
— Capacitor-run capacitance
0.000015
F
(default) | positive scalar
SI capacitor-run capacitance.
Dependencies
This parameter is exposed when Block choice
is set to Capacitor-start-capacitor-run
and the Parameterization unit parameter in the
Main settings is set to
SI
.
Capacitor-start resistance, Rs (pu)
— Capacitor-start resistance
0.0223
(default) | positive scalar
Per-unit capacitor-start resistance.
Dependencies
This parameter is exposed when Block choice is set to
Capacitor-start-capacitor-run
and the
Parameterization unit parameter in the
Main settings is set to Per
unit
.
Capacitor-start capacitance, Cs (pu)
— Capacitor-start capacitance
9.1232
(default) | positive scalar
Per-unit capacitor-start capacitance.
Dependencies
This parameter is exposed when Block choice is set to
Capacitor-start-capacitor-run
and the
Parameterization unit parameter in the
Main settings is set to Per
unit
.
Capacitor-run resistance, Rr (pu)
— Capacitor-run resistance
0.0669
(default) | positive scalar
Per-unit capacitor-run resistance.
Dependencies
This parameter is exposed when Block choice is set to
Capacitor-start-capacitor-run
or
Capacitor-start-capacitor-run
and the
Parameterization unit parameter in the
Main settings is set to Per
unit
.
Capacitor-run resistance, Cr (pu)
— Capacitor-run capacitance
0.000015
(default) | positive scalar
Per-unit capacitor-run capacitance.
Dependencies
This parameter is exposed when Block choice is set to
Capacitor-start-capacitor-run
or
Capacitor-start-capacitor-run
and the
Parameterization unit parameter in the
Main settings is set to Per
unit
.
Disconnection speed (% of rated speed)
— Disconnection speed
80
(default) | scalar in range [0,100]
Speed when capacitor is disconnected, expressed as a percentage of
rated speed. The value must be between 0
and
100
, inclusive.
Dependencies
This parameter is hidden when Block choice is
set to Main and auxiliary
windings
.
Mechanical
Rotor inertia
— Rotor inertia
0.01
kg*m^2
(default) | positive scalar
Rotor damping
— Rotor damping
0
N*m/(rad/s)
(default) | scalar
References
[1] Krause, P. C. "Simulation of
Unsymmetrical 2-Phase Induction Machines." IEEE Transactions on
Power Apparatus and Systems. Vol 84, Number 11, 1965, pp.
1025-1037.
Extended Capabilities
C/C++ Code Generation
Generate C and C++ code using Simulink® Coder™.
Introduced in R2018b