Implement transmission line with lumped parameters
Simscape / Electrical / Specialized Power Systems / Fundamental Blocks / Elements
The PI Section Line block implements an N-phase transmission line with parameters lumped in PI sections.
For a transmission line, the resistance, inductance, and capacitance are uniformly distributed along the line. An approximate model of the distributed parameter line is obtained by cascading several identical PI sections. The following figure shows one PI section of a three-phase transmission line.
Unlike the Distributed Parameters Line block, which has an infinite number of states, the PI section linear model has a finite number of states that permit you to compute a linear state-space model. The number of sections to be used depends on the frequency range to be represented.
An approximation of the maximum frequency range represented by the PI line model is given by the following equation:
where
Nbpi | Number of PI sections |
v | Propagation speed (km/s) = ; l in H/km, c in F/km |
ltot | Line length (km) |
For example, for a 100 km aerial line having a propagation speed of 300,000 km/s, the maximum frequency range represented with a single PI section is approximately 375 Hz. For studying interactions between a power system and a control system, this simple model could be sufficient. However for switching surge studies involving high-frequency transients in the kHz range, much shorter PI sections should be used. In fact, you can obtain the most accurate results by using a distributed parameters line model.
Note
The powergui block provides the RLC Line Parameters tool, which calculates resistance, inductance, and capacitance per unit of length based on the line geometry and the conductor characteristics.
For short line sections (approximately lsec <50 km) the RLC elements for each line section are simply given by:
where
r | Resistance per unit length (Ω/km) |
l | Inductance per unit length (H/km) |
c | Capacitance per unit length (F/km) |
f | Frequency (Hz) |
lsec | Line section length = ltot / N (km) |
However, for long line sections, the RLC elements given by the above equations must be corrected in order to get an exact line model at a specified frequency. The RLC elements are then computed using hyperbolic functions as explained below.
Per unit length series impedance at frequency f is
Per unit length shunt admittance at frequency f is
Characteristic impedance is
Propagation constant is
Hyperbolic corrections result in RLC values slightly different from the non-corrected values. R and L are decreased while C is increased. These corrections become more important as line section length is increasing. For example, let us consider a 735 kV line with the following positive-sequence and zero-sequence parameters (these are the default parameters of the Three-Phase PI Section Line block and Distributed Parameters Line block):
Positive sequence |
| |||
Zero sequence |
|
For a 350 km line section, noncorrected RLC positive-sequence values are:
Hyperbolic correction at 60 Hz yields:
For these particular parameters and long line section (350 km), corrections for positive-sequence RLC elements are relatively important (respectively −6.8%, −3.4%, and + 1.8%). For zero-sequence parameters, you can verify that even higher RLC corrections must be applied (respectively −18%, −8.5%, and +4.9%).
The PI Section Line block always uses the hyperbolic correction, regardless of the line section length.
Frequency f, in hertz (Hz), at which per unit length
r, l, c parameters are specified.
Hyperbolic correction is applied on RLC elements of each line section using this frequency.
Default is 60
.
The resistance per unit length, as an N-by-N
matrix in ohms/km (Ω/km). Default is 0.01273
.
The inductance per unit length of the line, as an
N-by-N matrix in henries/km (H/km). The terms in the
matrix diagonal cannot be zero, because it would result in an invalid propagation speed
computation. Default is 0.9337e-3
.
The capacitance per unit length of the line, as an
N-by-N matrix in farads/km (F/km). The terms in the
matrix diagonal cannot be zero, because it would result in an invalid propagation speed
computation. Default is 12.74e-9
.
The line length in km. Default is 100
.
The number of PI sections. The minimum value is 1. Default is
1
.
When the Number of phases [N] parameter is greater than
1
, the only measurement available in the drop-down menu is
Phase-to-ground voltages
.
When the Number of phases [N] is 1
, you can
select these options:
Select Input and output voltages
to measure the sending end (input
port) and receiving end (output port) voltages of the line model.
Select Input and output currents
to measure the sending end and
receiving end currents of the line model.
Select All pi-section voltages and currents
to measure voltages and
currents at the start and end of each pi-section.
Select All voltages and currents
to measure the sending end and
receiving end voltages and currents of the line model.
Default is None
.
Place a Multimeter block in your model to display the selected measurements during the simulation. In the Available Measurements list box of the Multimeter block, the measurement is identified by a label followed by the block name.
Measurement | Label |
---|---|
Sending end voltage (block input) |
|
Receiving end voltage (block output) |
|
Sending end current (input current) |
|
Receiving end current (output current) |
|
Phase-to-ground (block inputs and outputs) |
|
The power_piline
example